An attacker with the ability to modify a user program may change user program code on some ControlLogix, CompactLogix, and GuardLogix Control systems. Studio 5000 Logix Designer writes user-readable program code to a separate location than the executed compiled code allowing an attacker to change one and not the other. Additionally, devices communicating over the unauthenticated version of EtherNet/IP may be vulnerable to attacks from custom clients exploiting CVE-2021-22681 .
Read "The Old Switcheroo: Hiding Code on Rockwell Automation PLCs"
CVE-2022-1161
Rockwell Automation
Logix Controllers
10
Team82 is committed to privately reporting vulnerabilities to affected vendors in a coordinated, timely manner in order to ensure the safety of the cybersecurity ecosystem worldwide. To engage with the vendor and research community, Team82 invites you to download and share our Coordinated Disclosure Policy. Team82 will adhere to this reporting and disclosure process when we discover vulnerabilities in products and services.
Team82 has also made its public PGP Key available for the vendor and research community to securely and safely exchange vulnerability and research information with us.